IIS-375-I Application Notes
These application notes are updated occassionally for quick reference. If you are unable to find information regarding your IIS application here, please contact our IOTA Technical Services Team.
Maximum distance for operating a load
MAXIMUM DISTANCE FOR OPERATING A LOAD
The distance at which the IIS Inverter will operate a load is determined by three things:
1) The wattage of the load
2) The voltage (120V or 277V)
3) The gauge of the wire
Below is a reference chart to help determine the distance (in feet) allowing for a 3% voltage drop.
| |
120V |
277V* |
| Watts |
14 gauge |
12 gauge |
10 gauge |
14 gauge |
| 50 watts |
1600 ft |
2468 ft |
4084 ft |
8623 ft |
| 100 watts |
809 ft |
1249 ft |
2066 ft |
4311 ft |
| 125 watts |
646 ft |
997 ft |
1649 ft |
3445 ft |
| 150 watts |
537 ft |
829 ft |
1372 ft |
2874 ft |
| 200 watts |
404 ft |
624 ft |
1033 ft |
2155 ft |
| 250 watts |
323 ft |
493 ft |
827 ft |
1722 ft |
| 300 watts |
268 ft |
414 ft |
686 ft |
1437 ft |
| 350 watts |
230 ft |
356 ft |
589 ft |
1230 ft |
| 375 watts |
214 ft |
331 ft |
548 ft |
1146 ft |
*Incandescent lamps are not generally operated above 140 volts except by special permission by the authority having jurisdiction.